How to Parallel Current Transformers?

Current Transformer [CT] is used to obtain replica of primary current for use in metering or relaying applications. Though vast majority of applications only require one CT per phase, there could be situations where one or more feeders from the same phase need to be monitored. Examples are:

Parallel current transformer
Figure 1: Parallel current transformer
  1. Single meter need to combine load of two branch circuits.
  2. Due to large number of parallel cables, a single CT to encompass all cables may not be practical and hence parallel CT need to be used.

Read: How to select taps for multi ratio CT?

When it is desired to parallel multiple CT secondary, the following should be considered:

  • CT’s to be paralleled should have the same CT ratio and preferably same manufacturer and part number.
  • All CT’s that are paralleled should be installed using same polarity direction.
  • Secondary circuit of each CT need to be paralleled at or near the meter and not at the CT.
  • Use one common return for the CT return circuit.
  • Use one common ground for CT secondary circuit.
  • Voltage signal needs to be derived such that even if one feeder is turned OFF, the meter can record power data.
  • Meter or device connected need to be capable of carrying the sum of current from all the CT’s.
  • For ease of maintenance and troubleshooting it is good to have CT terminal (shorting) block. CT terminal block will help terminate multiple wires and also aid in testing and troubleshooting.
  • It is recommended to keep the CT lead length comparable between parallel CTs to keep the wire burden similar. If one CT is further away, then secondary lead wire diameter for that CT may have to be increased to keep the burden similar and prevent CT saturation.
  • Accuracy will not be degraded by paralleling if the combined current does not exceed the rated current of the meter.
  • It is recommended to clearly label or color code each wire to aid troubleshooting. 

Read: Neutral current transformer applied with electronic trip units

Sizing Parallel Current Transformer

When CTs are installed in multiple branch circuits, CT size must be equal to or greater than the sum of the maximum currents expected out of each branch circuit.

CT sizing example for two 400A loads
Figure 2: CT sizing example for two 400A loads

Example 1: If there are two branches and maximum load on each circuit is 400A then the CT primary rating needs to be atleast 400A+400A= 800A.  Assuming the meter is rated for 5A secondary, each 800: 5 CT would produce 2.5A giving a total full load secondary current of 5A to meter.

Read: Potential transformer accuracy class

If the CT was incorrectly sized at 400:5 per the full load (400A) of each branch and not the sum of each branch current, then the meter input current would be 5A+5A=10A thus overloading or possibly damaging the meter with 5A rated input.   

Read: Open circuit CT characteristics

Example 2: If there are three branches with load current of 200A, 300A and 500A, then each CT that need to be paralleled need to be 200A+300A+500A= 1000A primary rated.

Read: Adjusting current transformer ratio

Effective CT Ratio for Parallel Current Transformers

Read: CT open circuit protector

Accuracy for Parallel Current Transformers

Read: Zero sequence current transformer

Read: Three phase current metering using two current transformers