Nuisance Breaker Trip Due to Voltage Phase Angle Variation: Case Study

Affected circuit
Figure 1: Affected circuit

Read: Neutral current transformer applied with electronic trip units

Phase angle variation leading up to trip
Figure 2: Phase angle variation leading up to trip
Voltage vectors at time of trip
Figure 3: Voltage vectors at time of trip

Read: Current unbalance: Causes, Effects and Protection

Negative sequence vs phase angle for 277V system nominal voltage
Figure 4: Negative sequence vs phase angle for 277V system nominal voltage
  • Voltage Transformer (VT) measurement error/defect
  • Severe unbalanced line loading
  • Phase angle regulator malfunction
  • Use of triplex transformers with dissimilar characteristics
  • Unequal line impedance or lack of line transposition

Read: Circuit breaker trip due to control circuit ground fault

Source and load end voltage waveform: 12.47kV, A Phase load 1000kW, B&C load 10kW
Figure 5: Source and load end voltage waveform: 12.47kV, A Phase load 1000kW, B&C load 10kW

Read: Difference between control power transformer and potential transformer